Operating modes, Range mode, Rate mode – Rockwell Automation 1746-HSCE,D17466.5 High-Speed Counter Module User Manual

Page 15: Operating modes -3, Range mode -3 rate mode -3

Advertising
background image

Publication 1746-UM006B-EN-P - August 2005

Module Overview 1-3

Operating Modes

The module operates in 3 modes:

Range mode

Rate mode

Sequencer mode

Specific operating mode information is contained in Chapter 2,
Module Operation. The following information summarizes the
module’s operating modes.

Range Mode

In the Range Mode, you define a group of count ranges and define
the outputs to be active when the Accumulated Count value is within
each range. In this mode, the module offers:

up to 12 ranges

dynamically configurable ranges

ring or linear counter operation

input rate calculation

direct SLC processor control of unused outputs

Rate Mode

In the Rate Mode, you define a group of rate ranges and
corresponding outputs. When the Rate Measurement is within each
defined range, the corresponding outputs are active. In this mode, the
module offers:

Rate Periods from 10 ms to 2.55 seconds

input rates up to 32,767 Hz in either direction

up to 12 ranges

ring or linear counter operation

dynamically configurable Rate Period and range values

IMPORTANT

Appendixes D and E contain blank worksheets to
assist you when configuring your module. Appendix
D contains worksheets for Range and Rate Mode
operation. Appendix E contains worksheets for the
Sequencer Mode operation.