Publication 1756-UM528A-EN-P - April 2004

8-2 Troubleshooting the Sequence of Events Module

Table 8.2 describes how to use the Sequence of Events module’s LED
status indicators.

Using RSLogix 5000 To
Troubleshoot the Module

In addition to the LED status indicators on the module, RSLogix
5000 alerts you to fault and other conditions in one of three ways:

• Warning signal on the main screen next to the module – This

occurs when the connection to the module is broken.

Table 8.2

This indicator:

With this display:

Means:

Take this action:

OK

Steady green light

The inputs are being multicast and in normal
operating state.

None

Flashing green light

The module has passed internal diagnostics
but is not multicasting inputs.

Configure the module with RSLogix 5000.

Flashing red light

One of the following:

• Previously established

communication has timed out

• A FLASH update is in progress.

• Check controller and chassis

communication.

• Finish the update

Steady red light

An unrecoverable error has occurred on the
module.

Replace the module.

I/O State

Yellow

The input is active.

None

Warning icon appears when a
communications fault occurs or
if the module is inhibited