Choosing the extended-depth housing, Choosing the extended-depth housing -8 – Rockwell Automation 1756-IH16ISOE ControlLogix Sequence of Events Module User Manual

Page 34

Advertising
background image

Publication 1756-UM528A-EN-P - April 2004

3-8 Installing the Sequence of Events Module

Choosing the
Extended-Depth Housing

There are two housing options you must consider when wiring
your Sequence of Events module–standard-depth or extended-depth.

When you order an RTB for your module, you receive a
standard-depth housing with the RTB. If your application uses
heavy gauge wiring, you can order an extended-depth housing.
This housing does not come with an RTB.

You can use one of the housings listed in Table 3.2.

Figure 3.9 shows the difference, in terms of capacity, between the
housing options.

Figure 3.9

Table 3.2

Use this
housing:

with this RTB:

This combination allows up
to this capacity of wires:

1756-TBCH

Cage clamp

336 sq. mm

1756-TBS6H

Spring clamp (36-position)

1756-TBE

Any RTB that uses heavy
gauge wiring

628 sq. mm

IMPORTANT

The housings shown are used with a spring clamp
RTB, but the capacity for each remains the same
regardless of RTB type.

Standard-Depth Housing

Extended-Depth Housing

30484-M

Maximum Area = 336mm

2

36 - 18AWG wires
23 - 14AWG wires

Maximum Area = 628mm

2

40 - 14AWG wires

Advertising