Publication 1756-UM528A-EN-P - April 2004

Using The Sequence of Events Module in CST Per Point Mode 6-13

Figure 6.5 shows when to clear data from the Sequence of Events
module. In this example, the Sequence of Events module sent input
data to the controller, and the controller copied the relevant input data
to a separate structure. Now, the controller must clear the data from
the Sequence of Events module.

In this example, to clear data from the Sequence of Events module,
the controller writes the following to the Sequence of Events
output word:

• O.EventAck.2 = 1
• O.NewDataAck.2 = 1

Figure 6.5

If Latch CST is disabled, the controller does not need to clear
timestamp data. In this case, Sequence of Events module sends new
data, from subsequent transitions, to the controller as soon as they
occur. The controller overwrites timestamp data from the last
transition, regardless of whether it saved the data or not.

0 0 0 0 0 0 0
0 0 0 0 0 0 0

0 1 0 1 1 0 0
0 0 0 0 0 0 0

0 0 0 0 0 0 0
0 0 0 0 0 0 0

0 0 0 0 0 0 0
0 0 0 0 0 0 0

I.Fault

I.EventOverlow
I.ReturningUCTTime
I.EventNumber
I.Timestamp[16].OffOn[2]
I.Timestamp[16].OnOff[2]

I.Data
I.NewData

42793

1. Input 2 transitions

from OFF to ON.

2. Module timestamps

the transition.

3. Module sends

input data to
the controller.

Sequence of Events module

ControlLogix controller

Controller tags

Separate array

5. Controller clears data from input 2 on the Sequence of Events module.

O.EventAck.2 = 1
O.NewDataAck.2 = 1

I.Fault

I.EventOverlow

I.ReturningUCTTime
I.EventNumber
I.Timestamp[16].OffOn[2]
I.Timestamp[16].OnOff[2]

I.Data
I.NewData

4. Controller

copies
relevant
data from
controller
tags to a
separate
array.