Module tag names and definitions, Tags used in cst point per mode – Rockwell Automation 1756-IH16ISOE ControlLogix Sequence of Events Module User Manual

Page 136

Advertising
background image

Publication 1756-UM528A-EN-P - April 2004

D-2 Using Module Tags

Module Tag Names
and Definitions

The tags associated with the Sequence of Events module depends
on the type of module and the Communications Format chosen
during configuration. For each operational mode, there are three
sets of tags:

• Configuration
• Input
• Output

Tags Used in CST Point Per Mode

Configuration Tags

Table D.2 describes the configuration tags generated in RSLogix 5000
when you use the Sequence of Events module in CST Per Point Mode.

Table D.2 Configuration Tags in CST Per Point Mode

Tag name:

Type:

Description:

C.LatchEvents

BOOL

Latches events so that timestamp data from an input transition will not be
overwritten until acknowledged.

0 = CST not latched (default)

1 = CST latched

For more information on Latch CST, see page 5-7.

C.FilterOffOn

SINT

Sets the OFF to ON filter time for all 16 inputs. Times are set in 1ms increments from
0ms to 50ms.

0 = no filtering

For more information on Software Configurable Input Filters, see page 5-10.

C.FilterOnOff

SINT

Sets the ON to OFF filter time for all 16 inputs. Times are set in 1ms increments from
0ms to 50ms.

0 = no filtering

For more information on Software Configurable Input Filters, see page 5-10.

C.CaptureOffOn.x

DINT

Enables capturing OFF to ON events on a per point basis. If disabled (i.e., set to 0), that
point will not record timestamp data for OFF to ON input transitions.

0 = CST Capture disabled for OFF to ON input transitions - This option is useful if you
want to avoid using buffer space on the Sequence of Events module for events in which
you have no interest.

1 = CST Capture enabled (default) for OFF to ON input transitions

For more information on Enable CST Capture, see page 5-5.

Advertising