Rockwell Automation 1756-IH16ISOE ControlLogix Sequence of Events Module User Manual

Page 117

Advertising
background image

Publication 1756-UM528A-EN-P - April 2004

Specifications and Module Block Diagrams A-7

EFT/B Immunity

IEC 61000-4-4:
±4kV at 2.5kHz on signal ports

Surge Transient
Immunity

IEC 61000-4-5:
±1kV line-line (DM) and ±2kV line-earth (CM) on signal
ports

Conducted RF Immunity

IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz
to 80MHz

Oscillatory Surge
Withstand

IEEE C37.90.1:
3kV

Enclosure Type Rating

None (open-style)

Agency Certification
(when product is marked)

UL

UL Listed Industrial Control Equipment

CSA

CSA Certified Process Control Equipment

CSA

CSA Certified Process Control Equipment for
Class I, Division 2 Group A,B,C,D Hazardous
Locations

CE

(3)

European Union 89/336/EEC EMC Directive,
compliant with:

EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial

Requirements

EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions

European Union 73/23/EEC LVD Directive,
compliant with:

EN 61131-2; Programmable Controllers

C-Tick

(3)

Australian Radiocommunications Act,
compliant with:

AS/NZS CISPR 11; Industrial Emissions

(1)

Maximum wire size will require extended housing - 1756-TBE.

(2)

Use this Conductor Category information for planning conductor routing. Refer to Publication 1770-4.1,
“Industrial Automation Wiring and Grounding Guidelines”.

(3)

See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other
certification details.