Using the default configuration, Altering the default configuration – Rockwell Automation 1756-IH16ISOE ControlLogix Sequence of Events Module User Manual

Page 46

Advertising
background image

Publication 1756-UM528A-EN-P - April 2004

4-6 Configuring the Sequence of Events Module

Using the Default
Configuration

If you use the default configuration and click on Finish, you are done.

Altering the Default
Configuration

If you click Next in step 4 on page 4-4, you can write specific
configuration for your module in RSLogix 5000.

Some of the screens that appear during this initial module
configuration process are blank and are not shown here. However,
those screens can be important during online monitoring. To see
these screens in use, see Chapter 8, Troubleshooting the Sequence of
Events Module
.

Write specific configuration for your Sequence of Events module
on the following screens.

On this screen, you can:

A. Change the RPI. For more information

on the RPI, see page 2-6.

B. Inhibit the module. For more

information on inhibiting the module,
see page 5-15.

C. Make sure a Major Fault occurs on

the module’s owner-controller if there
is a connection failure between the
module and the controller.

D. Click Next until you see the

screen below.

On this screen, you can:

A. Enable CST Capture for each input

point. For more information on CST
Capture, see page 5-5.

B. Configure Chatter Detection for each

input point. For more information on
Chatter Detection, see page 5-8.

C. Set the Input Filter Times. For more

information on Input Filters, see
page 5-10.

D. Click on the box to enable CST

Latching. For more information on CST
Latching, see page 5-7.

E. Click Finish.

Advertising
This manual is related to the following products: