Rockwell Automation 1756-IH16ISOE ControlLogix Sequence of Events Module User Manual

Page 124

Advertising
background image

Publication 1756-UM528A-EN-P - April 2004

B-6 Integrating The HiProm GPS Module (1756HP-GPS) into a ControlLogix Sequence of Events Module System

How Does the ControlLogix
Controller Retrieve
Converted Value from the
1756HP-GPS Module?

Once a ControlLogix controller receives the timestamps from an event
cascade, it may send them to the 1756HP-GPS via a message
instruction for conversion to either the following formats:

• Wall clock time (WCT) - Format that is easily understood.

Typically, the controller requests a conversion to this format for
display purposes.

• UCT - This format is a 64-bit value in microseconds, similar to

CST except that UCT starts from 1 January 1972. It is most useful
to sort data using this field prior to converting to WCT for
display purposes.

To convert CST-format timestamps to WCT, you must:

1. Add the 1756HP-GPS module to your RSLogix 5000 project via

the Generic Module profile. For more information on how to
configure the 1756HP-GPS module in an RSLogix 5000 project,
see the 1756HP-GPS module user manual available at
http://www.hiprom.com.

2. Send a Message Instruction to the 1756HP-GPS module that uses

the configuration listed in Table B.1

Table B.1

Field:

Value:

Message Type

CIP Generic

Service Type

Custom

Service Code

32 (hex)

Class

70 (hex)

Instance

1

Attribute

1 (hex)

Source Element

Controller tag where the CST-format timestamp is located

Source Length

8

Destination

Destination tag for reply data

Advertising
This manual is related to the following products: