Rockwell Automation 1756-IH16ISOE ControlLogix Sequence of Events Module User Manual

Page 81

Advertising
background image

Publication 1756-UM528A-EN-P - April 2004

Using The Sequence of Events Module in CST Per Point Mode 6-9

Table 6.3 describes the data that is sent for each input. These tags are
sent to the controller immediately after the module timestamps a
transition on any input and at each RPI.

Table 6.3 Input Tags in CST Per Point Mode

Tag name:

Set on a Per Point or
Modulewide basis:

Description:

I.Fault

Per point

(1)

Indicates if a fault has occurred for the input.

0 = no fault
1 = fault – The fault can be chatter or communication fault as described below:

• Chatter - The Sequence of Events module can detect chatter on individual inputs

and will set the appropriate tag to 1 when chatter exists on an input. For
example, if the module has detected chatter on input 4, I.Fault.4 = 1.

• Communication fault - The controller sets this tag to 1 for all 32 bits if a

communication fault occurs on the module.

This tag clears when the fault that causes the condition no longer exists.

I.Data

Per point

(1)

Status of the input point. This data is filtered if the Input Filter feature is used on the
module. Thus, an input change must pass through the filter before it is seen in this tag.

0 = input is OFF
1 = input is ON

For example, if input 3 is ON, I.Data.3 = 1.

I.NewData

Per point

(1)

Flag indicating if new timestamp data was detected on the input.

0 = no new timestamp data on the input
1 = new timestamp data on the input (since last acknowledged)

Because input data for all inputs is sent immediately after each timestamped transition
and at each RPI, this tag is useful to quickly determine on which input the transition
occurred. For example, if the Sequence of Events module sends new input data to the
owner-controller and I.NewData.5 = 1, you know that at least one of the timestamps for
input 5 (i.e., I.Timestamp[5].OffOn or I.Timestamp[5].OnOff) has new data.

This tag only clears when the controller acknowledges the new data or all events on the
module are reset. For more information, see page 6-12.

I.EventOverflow

Per point

(1)

Set for an input when the module either:

• Does not timestamp a transition on the input – The module has Latch CST

enabled and a similar transition has already been timestamped on this input but
has not been cleared via the EventAck and NewDataAck output tags (see
page 6-12).

or

• Overwrites previously-recorded timestamp data for the input – The module has

Latch CST disabled and multiple transitions occur on the input. In this case,
timestamp data from new transitions are recorded before previously-recorded
transitions were cleared from the input via the EventAck and NewDataAck
output tags (see page 6-12).

This value is cleared if the module is reset.