Specifications and Module Block Diagrams A-5

1756-IH16ISOE
Specifications

Number of Inputs

16 (Individually isolated)

Module Location

1756 ControlLogix Chassis

Backplane Current

275mA @ 5.1V dc & 2mA @ 24V dc

Backplane Power

1.3W

Maximum Power Dissipation
(Module)

5.5W @ 60

o

C

Thermal Dissipation

17.22 BTU/hr.

On-State Voltage Range

90-140V dc

Nominal Input Voltage

125V dc

On-State Current

1.15mA @ 90V dc minimum
1.85mA @ 140V dc maximum

Maximum Off-State Current

0.3mA

Maximum Off-State Voltage

20V dc

Maximum Input Impedance

74.8k

Input Delay Time

OFF to ON

ON to OFF

Hardware Delay (10

µs nominal/20µs maximum)

+ Firmware Scan (25

µs)

+ Input Filter Time (User selectable time: 0ms to 50ms)
+ ASIC delay (175

µs - FIFO/625µs - CST Per Point)

Hardware Delay (50

µs nominal/75µs maximum)

+ Firmware Scan ((25

µs)

+ Input Filter Time (User selectable time: 0ms to 50ms)
+ ASIC delay (175

µs - FIFO/625µs - CST Per Point)

Timestamp accuracy

100

µs

Cyclic Update Time (RPI)

User selectable (250

µs minimum/750ms maximum)

Reverse Polarity Protection

Yes

Isolation Voltage

Inputs to backplane and
Input to input

250V continuous

RTB Screw Torque (Cage
clamp)

4.4 inch-pounds (0.4Nm) maximum

Module Keying (Backplane)

Software configurable

RTB Keying

User defined mechanical keying

RTB and Housing

36-Position RTB (1756-TBCH or TBS6H)