Related synchlink documentation – Rockwell Automation 1756-IH16ISOE ControlLogix Sequence of Events Module User Manual

Page 133

Advertising
background image

Publication 1756-UM528A-EN-P - April 2004

Synchronizing CSTs Across Multiple Chassis C-5

Figure C.3

Related SynchLink
Documentation

For more information on how to use the 1756-SYNCH module, see:

• SynchLink Design Guide, publication number 1756-TD008
• ControlLogix SynchLink Module User Manual, publication

number 1756-UM521.

Each chassis contains:

• 1756-L55 controller, version 11.71
• 1757-SRM module
• 1756-CNB(R) module (series D,

version 5.23 or greater)

These chassis are NOT synchronized.

ControlNet

SynchLink

43834

Chassis containing 1756-CNB(R)
module (series D, version 5.23 or
greater) and remote I/O but no
Sequence of Events or 1756-SYNCH
modules and not synchronized with
the other remote chassis.

Each chassis contains:

• Sequence of Events module
• 1756-SYNCH module
• 1756-CNB(R) module (series

D, version 5.23 or greater)

Chassis contains:

• 1756-L55 controller, version 13.x

– Required because the
redundant controllers use version
11.71. This controller is not
required if you use version 13
redundancy.

• Sequence of Events module
• 1756-SYNCH module
• 1756-CNB(R) module (series D,

version 5.23 or greater)

Primary chassis

Secondary chassis

Advertising