Rockwell Automation 1756-IH16ISOE ControlLogix Sequence of Events Module User Manual

Page 116

Advertising
background image

Publication 1756-UM528A-EN-P - April 2004

A-6 Specifications and Module Block Diagrams

Conductors

Wire Size

Category

#22 to #14 AWG (0.324 to 2.08 sq. mm) stranded

(1)

3/64 inch (1.2mm) insulation maximum
1

(2)

Screwdriver Blade Width for
RTB

1/8 inch (3.2mm) maximum

Environmental Conditions

Operational
Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 60°C (32 to 140°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating
Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating
Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged
Non-operating Thermal Shock):
-40 to 85°C (-40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged
Non-operating Damp Heat):
5 to 95% non-condensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):
2g @ 10-500Hz

Operating Shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30g

Non-operating Shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50g

Emissions

CISPR 11:
Group 1, Class A

ESD Immunity

IEC 61000-4-2:
6kV contact discharges
8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 80MHz to
1000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900Mhz
10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz