Publication 1756-UM528A-EN-P - April 2004

Integrating The HiProm GPS Module (1756HP-GPS) into a ControlLogix Sequence of Events Module System B-3

Using a 1756HP-GPS module, you can convert the CST-format
timestamps, received from a ControlLogix Sequence of Events
module, into a Gregorian wall clock time (WCT) that is easily
understood. Generally, the following occurs in this case:

1. The Sequence of Events module sends timestamps to the

controller after an event cascade.

2. The ControlLogix controller sends a message instruction to the

1756HP-GPS module with a CST-format timestamp; you must
use one MSG per timestamp.

3. The 1756HP-GPS module converts the CST-format timestamp to

UCT and Gregorian wall clock format.

4. 1756HP-GPS module send the new value back to the controller,

delivering the value in whatever format the controller requested
via the MSG configuration

Figure B.2

Controller

Sequence of
Events module

1756HP-GPS
module

Timestamps sent in CST format to controller

Timestamp sent in CST format via MSG to 1756HP-GPS

Timestamp converted from CST format to Gregorian and UCT format

Converted timestamp sent to controller