C-4 Synchronizing CSTs Across Multiple Chassis

Synchronizing Chassis in
ControlLogix Redundancy
Systems

When Sequence of Events modules are used in ControlLogix
Redundancy systems, the chassis that contain the Sequence of
Events modules must be synchronized.

Figure C.3 on page C-5 shows an example ControlLogix redundancy
system that uses Sequence of Events modules in some of its remote
chassis to timestamp input transitions and 1756-SYNCH modules to
synchronize CSTs among those remote chassis.

When synchronizing time in ControlLogix redundancy systems that
also use Sequence of Events modules, remember the following:

• A time master (either ControlLogix controller or 1756-SYNCH

module) must reside in each synchronized chassis.

• All chassis containing Sequence of Events modules must also

contain 1756-SYNCH modules that provide a common CST via
SynchLink.

IMPORTANT

At the time of this printing (April 2004),
ControlLogix Redundancy was only available with
ControlLogix controllers version 11.71. To
synchronize remote Sequence of Events modules,
you must either:

• Use version 13 redundancy across the system

or

• Use version 11.71 for the redundancy

controllers and include a ControlLogix
controller, version 13, in one of the
synchronized remote chassis, as shown in the
example.

In this case, you must use two RSLogix 5000
projects–one for the redundancy controllers
(programmed with RSLogix 5000, version 11)
and one for the remote chassis controller
(programmed with RSLogix 5000, version 13).