Wiring the sequence of events module, Wiring the sequence of events module -6 – Rockwell Automation 1756-IH16ISOE ControlLogix Sequence of Events Module User Manual

Page 32

Advertising
background image

Publication 1756-UM528A-EN-P - April 2004

3-6 Installing the Sequence of Events Module

Wiring the Sequence of
Events Module

Use Figure 3.7 to wire your Sequence of Events module.

Figure 3.7

WARNING

If you connect or disconnect wiring while the
field-side power is on, an electrical arc can occur.
This could cause an explosion in hazardous
location installations. Be sure that power is
removed or the area is nonhazardous before
proceeding.

40167-M

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

Non-isolated wiring

Isolated wiring

Daisy chain to other RTBs

DC (-)

Jumper bar
(Cut to length)

DC-5 (-)

DC-5 (+)

DC (+)

DC-0 (+)

DC-1 (+)

DC-0 (-)

DC-1 (-)

IN-0

IN-1

IN-2

IN-3

IN-8

IN-4

IN-5

IN-6

IN-7

Not used

IN-9

IN-10

IN-11

IN-12

IN-13

IN-14

IN-15

Not used

GND-0

GND-1

GND-2

GND-3

GND-8

GND-4

GND-5

GND-6

GND-7

Not used

GND-9

GND-10

GND-11

GND-12

GND-13

GND-14

GND-15

GND-15

DC-6 (-)

DC-6 (+)

NOTES:

1. All terminals with the same name are connected together on the module. For example, DC (-) can be connected to either terminal marked

GND-15.

2. When you use the second GND-15 terminal to daisy chain to other RTBs, always connect the daisy chain to the terminal directly connected

to the supply wire, as shown in the example above.

3. If separate power sources are used, do not exceed the specified isolation voltage.

4. Do not connect more than 2 wires to any single terminal.

5. The jumper bar part number is 97739201. Contact your local Rockwell Automation sales representative to order jumper bars, if necessary.

Sink input wiring

Source input wiring

Source input wiring

Sink input wiring

Advertising