Rockwell Automation 1757-FFLD Linking Device Configuration Manual User Manual
Page 101
Advertising
![background image](/manuals/579914/101/background.png)
Publication 1757-PM002A-EN-E - June 2006
Applications 4-47
Ratio PID Logic
Block
Block Type Parameter
Element
Value
CON FLOW
Analog
Input
MODE_BLK
TARGET
Auto
XD_SCALE (these
values must match
the
PRIMARY_VALUE_
RANGE of the
transducer block)
EU_100
EU_0
UNITS_DECIMAL
DECIMAL
CHANNEL
1
L_TYPE
Direct
PID
PID
MODE_BLK
TARGET
CAS
GAIN
Loop
Dependent
RESET
RATE
PV_SCALE (these
values must match
in Analog Input
range)
EU_100
EU_0
UNITS_DECIMAL
DECIMAL
UNC FLOW
Analog
Output
MODE_BLK
TARGET
Auto
XD_SCALE (these
values must match
the
PRIMARY_VALUE_
RANGE of the
transducer block)
EU_100
EU_0
UNITS_DECIMAL
DECIMAL
CHANNEL
1
L_TYPE
Direct
RATIO
Arithmetic
MODE_BLK
TARGET
Auto
ARITH_TYPE
Traditional
summer
GAIN
ratio
IN_1
STATUS
GNC
IN_2
STATUS
GNC
IN_3
STATUS
GNC