Appendix c - limitations, Limitations, Appendix – Rockwell Automation 1757-FFLD Linking Device Configuration Manual User Manual
Page 129
Advertising
![background image](/manuals/579914/129/background.png)
1
Publication 1757-PM002A-EN-E - June 2006
Appendix
C
Limitations
General Limitations
Item
Enforcement
Limit
Comment
VCR
FFLD
128 Total
16 in/16 out per H1
Function Blocks
Server
8 (no license, demo)
64, 256, 1024
Activation dependent
Devices
Server
80 or 520 (FFLD
included in count)
IDShellHSE.dll
dependent
Suggested Limitations
Segment Usage
Macrocycle times (mS)
Devices/H1 Segment
I/O
1000–2000
12–16
simple loop control
700–1000
6–8
fast loop control
500–700
4–5
critical loop control
300–500
2–3
Advertising