Rockwell Automation 1757-FFLD Linking Device Configuration Manual User Manual
Page 105
Advertising
Publication 1757-PM002A-EN-E - June 2006
Applications 4-51
Split Range PID Logic
Block
Block Type
Parameter
Element
Value
PRESSURE
Analog Input
MODE_BLK
TARGET
Auto
XD_SCALE *
EU_100
EU_0
UNITS_DECIMAL
DECIMAL
CHANNEL
1
L_TYPE
Direct
PID
PID
MODE_BLK
TARGET
CAS
GAIN
Loop
Dependent
RESET
RATE
PV_SCALE (these
values must
match in Analog
Input range)
EU_100
EU_0
UNITS_DECIMAL
DECIMAL
SPLIT
Splitter
MODE_BLK
TARGET
CAS
IN_ARRAY **
0,48,50,100
OUT_ARRAY **
100,0,0,100
VENT
Analog Output
MODE_BLK
TARGET
CAS
XD_SCALE *
EU_100
EU_0
UNITS_DECIMAL
DECIMAL
CHANNEL
1
L_TYPE
Direct
N2
Analog Input
MODE_BLK
TARGET
CAS
XD_SCALE *
EU_100
EU_0
UNITS_DECIMAL
DECIMAL
CHANNEL
1
L_TYPE
Direct