Publication 1757-PM002A-EN-E - June 2006

5-6 Troubleshooting

Can the Linking Device Be “Pinged” From the PC Host?

Yes:

a. Go to step “Does RSLink in the AB_ETHIP driver see the linking

device when RSWho is running?”

Are the Linking Device and the PC Host on the Same Sub-Net?

No:

Linking Device IP address: XXX.YYY.ZZZ.abc

PC Host IP address: XXX.YYY.ZZZ.def

a. In most cases, the linking device and the PC Host must be on the

same sub-nets. That is the XXX.YYY.ZZZ portion of the IP address
must match.

b. If you don’t know or cannot set the IP address of the linking device

using the DHCP/BootP server, call tech Support.

c. Change the IP address of the PC Host to match the sub-net of the

linking device.

Does RSLinx in the AB_ETHIP Driver See the Linking Device When RSWho is
Running?

No:

a. Verify that the AB_ETHIP-1 driver is properly configured.
b. Call Tech Support

Is the RSFieldbus Project Properly Configured?

Don’t know:

a. Refer to Create A New RSFieldbus Project on page 4-14 and

configure a project, or use a known good project file to test the
operation of the linking device on HSE. If this does not work,
contact Tech Support for assistance in building a proper project file.

Yes:

a. Remove power from the linking device.
b. On the top of the linking device, move the jumper to the left-most

contact position then back to the right-most contact position.

c. Close RSFieldBus.