Publication 1757-PM002A-EN-E - June 2006

Applications 4-15

3. Select Resource Block for the Block Type.

4. Enter >FFLD Resource< for the Block Tag.

5. Click OK.

The Block is added to the project.

6. Right-click the Resource Block and select Off Line Characterization.

The Off Line window opens.

To view all of the parameters, click

and maximize the

Characterization window.

7. Expand the MODE_BLK parameter.

8. Select TARGET, then click in the Value column and select Auto.

9. Click End Edit (or press <Enter>) to complete the edit.

Auto is shown next to TARGET.

10. Click Close.

The MODE_BLK parameter icon is shown under the Resource Block
icon.