Rockwell Automation 1757-FFLD Linking Device Configuration Manual User Manual

Page 45

Advertising
background image

Publication 1757-PM002A-EN-E - June 2006

Basic Function Blocks 3-7

• QUB: Queued User-triggered Bidirectional

The quantity of each class of VCR that is available for configuration and
communication is device dependent. The quantities are specified in the DD
files, which are provided with each device. An example of the quantities
defined in a DD file, specifically the *.cff file, is shown below.

As can be seen, the quantities are broken into sub-categories depending on
usage. The above example states that the device can have more publisher BNU
than subscriber BNU. Additionally, the device has no client QUB VCR, but it
has the ability to serve 8 server QUB VCR. Currently, these limits manifest
themselves in either download or communication errors when they are
exceeded.

There is also a nuance to the quantities that need to be emphasized with regard
to linking devices. The 1757-FFLD *.cff file is used below as an example.

Table 3.1 : VCR Classes

BNU

QUU

QUB

Permitted Roles

Publisher, Subscriber Source, Sink

Client, Server, Peer

Conveyance Paths

1

1

2

Conveyance Policy

Buffered

Queued

Queued

Transmission Policy

Network Scheduled

User Triggered

User Triggered

// From VcrListCharacterisitcs

MaxEntries

= 44

NumPermanentEntries

= 44

DynamicsSupportedFlag

= FALSE //Rev 1.5

StatisticsSupported

= 0x0 //Rev 1.5

MaximumNumberOfClientVcrs

= 0

MaximumNumberOfServerVcrs

= 5

MaximumNumberOfSourceVcrs

= 8

MaximumNumberOfSinkVcrs

= 0

MaximumNumberOfPublisherVcrs

= 19

MaximumNumberOfSubscriberVcr
s

= 12

// From VcrListCharacterisitcs

MaxEntries

= 44

NumPermanentEntries

= 44

DynamicsSupportedFlag

= FALSE //Rev 1.5

StatisticsSupported

= 0x0 //Rev 1.5

MaximumNumberOfClientVcrs

= 0