Rockwell Automation 1757-FFLD Linking Device Configuration Manual User Manual

Page 113

Advertising
background image

Publication 1757-PM002A-EN-E - June 2006

Troubleshooting 5-7

d. On the PC Host in the c:\Program Flies\Rockwell

Software\RSFieldbus\OLEServers\ directory delete the
IDShellHSE.bin file.

e. Restart RSFieldBus.
f. Load your project.
g. Apply power to the linking device. Allow the linking device to

completely start up as indicated by the H1 channel activity LEDs
blinking.

h. Go online in RSFieldBus and monitor the HSE Live List. The linking

device should now be visible.

i. If the linking device is still not visible in the HSE Live List, contact

Tech Support.

What To Do if The Linking
Device Does Not Appear in
the H1 Live List

Does the linking device appear in the HSE Live List?

No:

a. Go to What To Do if the FFLD Does Not Appear in the HSE Live

List on page 5-5.

Yes:

a. Close the H1 live List window.
b. Close the H1 network window.
c. Reopen the H1 network window.
d. Reopen the H1 Live List window.

Does the Linking Device appear in the H1 Live List Now?

Yes: Done.

Is the Linking Device Connected to the Network?

No:

a. Connect the linking device to the network following the instructions

in the Foundation Fieldbus Installation Guide.

Or:

a. Verify that the network connections are correct on the linking device

connector.

b. Verify that the network cable is connected to the network and that

the polarity is correct.

c. Verify that there are two and only two terminators on the network.

Advertising