4-18 Applications

3. Right-click the Process Cell icon and click Expand.

The Process Cell window opens.

4. In the Process Cell window, right-click the Process Cell icon and select

New Control Module.

5. Enter >Pressure< for the Tag and click OK.

The Pressure Control Module is added to the Project.

6. Right-click the Pressure icon and select Strategy.

The Strategy window opens.

Add Function Blocks to the Strategy

1. In the Strategy window, click Options ⇒ Function Block Icons ⇒

Rectangle.

2. Drag and drop the FFLD LGX, FI302 AO and LD292 AI blocks from

the H1-1 Fieldbus window to the Strategy window to resemble the
picture below.

Create Links

To create Fast Links, refer to the linking device user manual, publication
1757-UM010.

1. In the Strategy window, click the Link button

.

2. Click the AI Block.

The Output Parameter Selection window opens.

3. Select the OUT pin.

The pin fills to show that it is selected.