Rockwell Automation 1757-FFLD Linking Device Configuration Manual User Manual
Page 72

Publication 1757-PM002A-EN-E - June 2006
4-18 Applications
3. Right-click the Process Cell icon and click Expand.
The Process Cell window opens.
4. In the Process Cell window, right-click the Process Cell icon and select
New Control Module.
5. Enter >Pressure< for the Tag and click OK.
The Pressure Control Module is added to the Project.
6. Right-click the Pressure icon and select Strategy.
The Strategy window opens.
Add Function Blocks to the Strategy
1. In the Strategy window, click Options ⇒ Function Block Icons ⇒
Rectangle.
2. Drag and drop the FFLD LGX, FI302 AO and LD292 AI blocks from
the H1-1 Fieldbus window to the Strategy window to resemble the
picture below.
Create Links
To create Fast Links, refer to the linking device user manual, publication
1757-UM010.
1. In the Strategy window, click the Link button
.
2. Click the AI Block.
The Output Parameter Selection window opens.
3. Select the OUT pin.
The pin fills to show that it is selected.