Publication 1757-PM002A-EN-E - June 2006

4-20 Applications

15. Select the IN_1 pin and click OK.

Your Strategy window should look like this.

Download the Configuration

Before Downloading you must complete the Export Tags function. This
allows you to view Function Block parameters in the On Line mode.

Export Tags

1. In the Project window, right-click the Project name (in this case, PID),

and select Export Tags.

The Export Tags window opens.

2. Click Save to accept the default file name.

3. Click Yes to the Export Tags window question and replace the file.

4. Click OK to acknowledge that the Tags were exported successfully.

Download

It is important that the Macrocycle times for the HSE and the H1-1 networks
match for download purposes. This will aid the download process and
communications synchronization between the HSE and the H1-1 networks.

1. In the HSE Fieldbus window, right-click the HSE icon and select

Attributes.