Rockwell Automation 1757-FFLD Linking Device Configuration Manual User Manual

Page 70

Advertising
background image

Publication 1757-PM002A-EN-E - June 2006

4-16 Applications

Add Function Blocks to the Devices

Use the table below and the procedure from Add Function Blocksto add
additional Function Blocks to the devices.

Tag names should not have spaces in them for proper OPC communications..

Device

Block Type

Block Tag

Parameter

Element

Value

FFLD

Resource

FFLD_Resource

MODE_BLK

TARGET

Auto

ALERT_KEY

1

Logix

FFLD_LGX

MODE_BLK

TARGET

Auto

ALERT_KEY

1

SLOT (this value is used by
ControlLogix)

0

FI302

Resource

FI302_RES

MODE_BLK

TARGET

Auto

ALERT_KEY

1

Transducer

FI302_TXD

MODE_BLK

TARGET

Auto

ALERT_KEY

1

TERMINAL_NUMBER

1

Analog Output

FI302_AO

MODE_BLK

TARGET

CAS

ALERT_KEY

1

XD_SCALE (these values must
match the FINAL_VALUE_RANGE of
the transducer block

EU_100

20

EU_0

0

UNITS_DECIMAL

mA

DECIMAL

2

CHANNEL (this must match the
TERMINAL_NUMBER of the
transducer block

1

LD292

Resource

LD292_RES

MODE_BLK

TARGET

Auto

ALERT_KEY

1

Transducer

LD292_TXD

MODE_BLK

TARGET

Auto

ALERT_KEY

1

Analog Input

MODE_BLK

TARGET

Auto

ALERT_KEY

1

XD_SCALE (these values must
match the FINAL_VALUE_RANGE of
the transducer block

EU_100

5080

EU_0

0

UNITS_DECIMAL

mm H20 (68°F)

DECIMAL

2

CHANNEL

1

L_TYPE

Direct