4-16 Applications
Add Function Blocks to the Devices
Use the table below and the procedure from Add Function Blocksto add
additional Function Blocks to the devices.
Tag names should not have spaces in them for proper OPC communications..
Device
Block Type
Block Tag
Parameter
Element
Value
FFLD
Resource
FFLD_Resource
MODE_BLK
TARGET
Auto
ALERT_KEY
1
Logix
FFLD_LGX
MODE_BLK
TARGET
Auto
ALERT_KEY
1
SLOT (this value is used by
ControlLogix)
0
FI302
Resource
FI302_RES
MODE_BLK
TARGET
Auto
ALERT_KEY
1
Transducer
FI302_TXD
MODE_BLK
TARGET
Auto
ALERT_KEY
1
TERMINAL_NUMBER
1
Analog Output
FI302_AO
MODE_BLK
TARGET
CAS
ALERT_KEY
1
XD_SCALE (these values must
match the FINAL_VALUE_RANGE of
the transducer block
EU_100
20
EU_0
0
UNITS_DECIMAL
mA
DECIMAL
2
CHANNEL (this must match the
TERMINAL_NUMBER of the
transducer block
1
LD292
Resource
LD292_RES
MODE_BLK
TARGET
Auto
ALERT_KEY
1
Transducer
LD292_TXD
MODE_BLK
TARGET
Auto
ALERT_KEY
1
Analog Input
MODE_BLK
TARGET
Auto
ALERT_KEY
1
XD_SCALE (these values must
match the FINAL_VALUE_RANGE of
the transducer block
EU_100
5080
EU_0
0
UNITS_DECIMAL
mm H20 (68°F)
DECIMAL
2
CHANNEL
1
L_TYPE
Direct