254 - analog velocity offset, Ter 256, Analog current offset – Rockwell Automation 2098-DSD-xxx Ultra3000 Digital Servo Drives with DeviceNet User Manual

Page 97

Advertising
background image

Publication 2098-RM001C-EN-P – August 2002

Programming Reference

2-81

231

Set

Single-Turn
Absolute

USINT

1

Enables absolute position functionality when a
single-turn absolute (SRS) encoder is used as a
feedback device.
0 - Disable (default)
1 - Enable

232-252

Get

Reserved

USINT

1

Default: 0

253

Set

Analog Velocity
Scale

INT

2

%

Analog velocity scale applied to the analog input
when used for the velocity command. The scale is in
units of percentage of maximum motor speed per 10
Volts.
Range: -200 to 200
Default: 100

254

Set

Analog Velocity
Offset

INT

2

mV

Analog velocity offset applied to the analog input
when used for the velocity command.
Range: -10000 to 10000
Default: 0

255

Set

Analog Current
Scale

INT

2

%

Analog current scale applied to the analog input
when used for the current command. The scale is in
units of percentage of the minimum of the motor
intermittent current rating and drive intermittent
current rating, per 10 Volts.
Range: -400 to 400
Default: 100

256

Set

Analog Current
Offset

INT

2

mV

Analog current offset applied to the analog input
when used for the current command.
Range: -10000 to 10000
Default: 0

257

Set

Analog Position
Scale

INT

2

Cnts /
V

Analog position scale applied to the analog input
when used for the position command. The scale is in
units of counts/Volt.
Range: -32767 to 32767
Default: 1000

258

Set

Analog Position
Offset

INT

2

mV

Analog position offset applied to the analog input
when used for the position command.
Range: -10000 to 10000
Default: 0

259

Set

Limit Analog
Accel

USINT

1

Indicates if the analog acceleration limits are
enabled or disabled when the drive is in Analog
Velocity Input mode
0 - Disable (default)
1 - Enable

260

Set

Analog Accel
Limit

UDINT

4

Cnts /
Sec

2

The acceleration limit used when the drive is in
Analog Velocity Input mode and Parameter 259,
Limit Analog Accel is set to 1 - Enable.
Range: 0 to 0x7fffffff
Default: 100000

Parameter Object,
Instances ID = 1- 996

Parameter
Instance

Access
Rule

Parameter
Name

Data
Type

Data Size
(Bytes)

Units /
Scale

Description

Advertising