Removal Procedure
Follow the procedure below to remove roll-out chassis units from an MCC.
1. Open door of MCC.
2. Remove two screws to detach the lower wireway cover, if presently
attached. Refer to Figure 3.1.
Figure 3.1 Removing the Lower Wireway Cover
3. Remove shipping brace (if present).
4. Remove a total of four screws to detach both of the lower reinforcing
angles as shown in Figure 3.2 (used in D, E, F-frame 2362 units and in K
and L-code 2364F units).
!
ATTENTION: To avoid the hazard of electrical shock, verify
that all voltages on the system bus network have been discharged
before attempting to service the system.