Removal procedure, Removal procedure -2 – Rockwell Automation 2300 Family of Drive Systems Hardware User Manual

Page 34

Advertising
background image

3-2

Removing and Installing Roll-Out Chassis Units

Removal Procedure

Follow the procedure below to remove roll-out chassis units from an MCC.

1. Open door of MCC.

2. Remove two screws to detach the lower wireway cover, if presently

attached. Refer to Figure 3.1.

Figure 3.1 Removing the Lower Wireway Cover

3. Remove shipping brace (if present).

4. Remove a total of four screws to detach both of the lower reinforcing

angles as shown in Figure 3.2 (used in D, E, F-frame 2362 units and in K
and L-code 2364F units).

!

ATTENTION: To avoid the hazard of electrical shock, verify
that all voltages on the system bus network have been discharged
before attempting to service the system.

Lower Wireway
Cover

(TYP)

Example of Typical
Shipping Brace

Advertising