Rockwell Automation 2300 Family of Drive Systems Hardware User Manual
Page 48

5-8
Installing Offset Power Bus Splices
Installing Offset Power Bus Splices: Single Bar
For each power bus in the system, follow this procedure:
1. Verify that the following splice hardware is present:
2.
3. Verify that contact surfaces are free of dirt/debris. Deburr edges as
necessary.
4. Insert the bus clamps as indicated in Figure 5.5.
If each power bus consists of:
Then go to:
A single bar
Installing Offset Power Bus Splices: Single Bar
Two bars
Installing Offset Power Bus Splices: Dual Bar
Description
Common DC
Bus Quantity
Common AC
Bus Quantity
8-hole, offset busbar splice
2
3
Bus clamps
!
8
12
Flat washer
16
24
Nut/conical-spring washer
16
24
! For each busbar end with built-in clamps, decrease the required quantity by 2.
!
ATTENTION: Verify that the busbar splices are of the same
thickness as the busbars to be spliced.
For lineups containing common bus F-frame 2362 units, any
G-frame 2362 units, or M/N-code 2364F units, the bus splices
should be sized to match the overall bus rating of the lineup. See
Figure 5.2 for an example.