Installing Offset Power Bus Splices: Dual Bar
For each power bus in the system, follow this procedure:
1. Verify that the following splice hardware is present:
2. Verify that contact surfaces are free of dirt/debris. Deburr edges as
necessary.
3. Insert the bus clamps as indicated in Figure 5.6.
Description
Common DC
Bus Quantity
Common AC
Bus Quantity
8-hole, offset busbar splice
4
6
Bus clamps
!
8
12
Flat washer
16
24
Nut/conical-spring washer
16
24
! For each busbar end with built-in clamps, decrease the required quantity by 2.
!
ATTENTION: Verify that the busbar splices are of the same
thickness as the busbars to be spliced.