Rockwell Automation 57C329 Remote I/O Communications, AutoMax User Manual

Page 122

Advertising
background image

KĆ4

fiberĆoptic link with the transceiver hub. The transceiver is shipped

with dust caps covering the fiberĆoptic ports. The dust caps should

not be removed until the fiberĆoptic cables are installed, and should

be replaced if the cables are disconnected, to prevent dust

accumulation and the resulting loss of signal integrity.

WARNING

TURN OFF AND LOCKOUT OR TAG POWER TO BOTH THE MASTER OR SLAVE

DROP AND THE CORRESPONDING RACKĆMOUNTED OR STANDĆALONE

TRANSCEIVER BEFORE VIEWING THE FIBERĆOPTIC CABLE OR

TRANSMITTER

UNDER

MAGNIFICATION.

VIEWING

A

POWERED

FIBERĆOPTIC

TRANSMITTER

OR

CONNECTED

CABLE

UNDER

MAGNIFICATION MAY RESULT IN DAMAGE TO THE EYE. FOR ADDITIONAL

INFORMATION, REFER TO ANSI PUBLICATION Z136.1Ć1981. FAILURE TO

OBSERVE THIS PRECAUTION COULD RESULT IN BODILY INJURY.

The green LEDs on either side of each connector indicate the status

of the receiver and transmitter and will flicker as data is received and

transmitted by the transceiver.
The opposite end of the transceiver contains a sixĆscrew terminal

block for operating power and signal connections. See section K2.2

for the terminal block designations. The 24VDC required for

transceiver operation must be provided externally. Note that terminal

6 (-24V) is internally connected to the transceiver enclosure.
A jumper between terminals 3 and 4 is used to connect a builtĆin 120

ohm terminating load between terminals 1 and 2. This jumper must

be used on all StandĆAlone Transceivers.

1234

56

Receive LED

6Ćposition

Terminal Block

Transmit LED

FiberĆoptic

Ports

Figure K1.2 Ć StandĆAlone Transceiver

K1.2.4

FiberĆOptic Rack with Power Supply

The FiberĆOptic Rack and Power Supply (M/N 57C368) provide the

mechanical means of mounting and providing power for up to 10

fiberĆoptic transceivers (M/N 57C367). Technical specifications are

listed in Appendix A.

Advertising