3.5.2

Installing the Shark Interface Module

Use the following procedure to install the Shark Interface module:
Step 1.

Stop any application tasks that may be running.

DANGER

THIS EQUIPMENT IS AT LINE VOLTAGE WHEN AĆC POWER IS CONNECTED.

DISCONNECT AND LOCK OUT ALL UNGROUNDED CONDUCTORS OF THE AĆC

POWER LINE. FAILURE TO OBSERVE THESE PRECAUTIONS COULD RESULT

IN SEVERE BODILY INJURY OR LOSS OF LIFE.

Step 2.

Turn off power to the Shark rack including any power to

the wiring leading to the rack. For rack mounting and

power supply wiring information, refer to the Shark XL I/O

System instruction manual, J2Ć3018.

Step 3.

Take the module out of its shipping container. Be careful

not to touch the connectors on the back of the module.

Step 4.

Place the Shark Interface module in the first slot to the

right of the Power Supply module. Be sure the module is

wellĆseated in the rack.

Step 5.

Set the drop number of the Shark Interface module using

the 16Ćposition rotary switch on the module faceplate.

Valid drop numbers for racks containing both analog and

digital modules are 1 through 7. Valid drop numbers for

racks containing only digital modules are 9 through F.

Refer to section 2.3.
Note that the drop number is read only upon power up. If

the drop number is to be changed, power must be cycled

for the new number to be recognized.

Step 6.

Connect the drop cable (M/N 57C381 if you have a coaxial

cable network, M/N 57C366 if you have a fiberĆoptic

network) to the 9Ćpin connector on the module faceplate.

The end of the cable that connects to the module is

labeled COMM."

Step 7.

Turn on power to the rack. The Shark Interface module

automatically executes its powerĆup diagnostics. If no

errors are detected, the green CPU OK LED will be on. If

the LED is off, refer to chapter 6 for troubleshooting

information.
If the powerĆup diagnostics detect an invalid drop number,

the green COM OK LED will flash. Change the setting of

the 16Ćposition rotary switch and cycle power to clear the

invalid drop number.

Step 8.

If you are connecting the module to a fiberĆoptic network,

go to step 10. If you are connecting to a coaxial cable

network, continue to step 9.

Step 9.

To connect the module to a coaxial cable network,

connect the drop cable to the Communications Passive

Tap (M/N 57C380). The end of the cable that connects to

the passive tap is labeled TAP." Figure 3.1 shows the

Shark Interface module connected to the Remote I/O

network. Continue to step 11.