3Ć33

P

/

S

P

R

O

C

E

S

S

O

R

P

/

S

NEW DROP

NEW CABLE SEGMENT

BNC CONNECTOR

75 OHM

TERMINATING

LOAD

PASSIVE

TAP

DROP

CABLE

R

E

M

O

T

E

R

E

M

O

T

E

I/O

I/O

Figure 3.26 Ć Adding aNew Rack Drop to the End of the Remote I/O

Network (Coax)

Step 6.

If a new drop is to be added along the cable route, use the

following procedure:
a.) Cut the remote I/O cable at the point where the new

drop is to be added.

b.) Terminate the cable ends with BNC connectors and, if

necessary, splice them with the new cable segments.

Test the spliced cable segments following the

instructions provided in section 3.4.

c.) For rack drops, connect the other ends of the new

cable segments with a tap attached to the new drop as

shown in figure 3.27. For Head drops, connect the

ends of the new cable segments to a BNC Tee

Adapter. Connect the Tee Adapter directly to the

Remote I/O Head or Remote Drive Interface Head.

Step 7.

Make sure the drop number of the newlyĆadded Remote

I/O module, Shark Interface module, Remote I/O Head, or

Remote Drive Interface Head is properly selected before

you cycle power and resume Remote I/O network

operation.

Monitor drop 0 for the status of all remote drops to verify that no

drops have been adversely affected by the installation.