7 adding a slave drop to the remote i/o network – Rockwell Automation 57C329 Remote I/O Communications, AutoMax User Manual

Page 58

Advertising
background image

3Ć32

3.7

Adding a Slave Drop to the

Remote I/O Network

Use the following procedure to add a Multibus rack, a Shark rack, a

Remote I/O Head, or a Remote Drive Interface Head as a slave drop

on the coaxial cable network:
Step 1.

Identify the route for the new cable segment(s). Refer to

the recommendations provided in section 3.3. If the new

drop is to be added at the end of the network, only one

new cable segment will be necessary. Otherwise, two new

cable segments may be needed.

Step 2.

Calculate the new cable segment length. Ensure the new

total cable length does not exceed the maximum cable

length of 3,000 feet as defined in the network cable

specifications in Appendix F. If it exceeds 3,000 feet,

consult with Reliance Electric before going on to the next

step.

Step 3.

Cut, install, terminate, and test the new cable segment

following the instructions provided in sections 3.4.

Step 4.

Stop all application tasks.

Step 5.

Refer to figure 3.26 and use the following procedures if a

new rack drop is to be added to one of the ends of the

network. Go to step 6 if a rack drop is to be added along

the cable route.
a.) Disconnect the terminating load from the tap of the

existing drop and replace it with one end of the new

cable segment.

b.) If you are adding a slave rack drop, connect the

terminating load to a new tap. If you are adding a

Head drop, connect the terminating load to a new BNC

Tee Adapter. Connect the other end of the new cable

segment to this tap (or BNC connector).

c.) Using a drop cable, attach the Remote I/O module or

the Shark Interface module to the new tap. For Head

drops, connect the BNC Tee Adapter directly to the

Remote I/O Head or Remote Drive Interface Head.

d.) Go to step 7.

Advertising