Step 9.

Turn on power to the rack. The module automatically

executes its powerĆup diagnostics. If no errors are

detected, the green CPU OK LED will turn on. If the LED is

off, refer to chapter 6 for troubleshooting information.

Step 10. Check the status of the master Remote I/O module's

green NETWORK ACTIVE LED. The LED should be on. If

the LED is off, refer to chapter 6 for help in troubleshooting

a communication problem.

3.6.3

Replacing the Remote I/O Head (M/N 57C328 and

M/N 57C330)

Use the following procedure to replace the Remote I/O Head:
Step 1.

Stop any application tasks that may be running.

Step 2.

Disconnect the BNC Tee Adapter that connects the

Remote I/O Head to the Remote I/O network.

DANGER

THIS EQUIPMENT IS AT LINE VOLTAGE WHEN AĆC POWER IS CONNECTED.

DISCONNECT AND LOCK OUT ALL UNGROUNDED CONDUCTORS OF THE AĆC

POWER LINE. FAILURE TO OBSERVE THESE PRECAUTIONS COULD RESULT

IN SEVERE BODILY INJURY OR LOSS OF LIFE.

Step 3.

Turn off power to the Remote I/O Head including any

power to the wiring leading to the Remote I/O Head.

Step 4.

Disconnect the I/O cables from the I/O port connectors.

Step 5.

Using a screwdriver, remove one of the screws from the

plastic guard covering the terminal strip and slide the

guard to the left to expose the terminals.

Step 6.

Disconnect the input power wires.

Step 7.

Disconnect the green grounding wire.

Step 8.

Remove the #10 bolts and remove the Remote I/O Head

from the mounting surface.

Step 9.

Attach the replacement Remote I/O Head to the mounting

surface using #10 (M5) bolts or studs.

Step 10. Connect the green grounding wire.
Step 11. Using a screwdriver, remove one of the screws from the

plastic guard covering the terminal strip and slide the

guard to the left to expose the terminals.

Step 12. Connect the input power wires. (Refer to section 3.5.3 and

figure 3.21 for input power connection.)

Step 13. Slide the guard back to cover the terminal strip and

replace the screw.

Step 14. Set the drop number (1Ć7) of the Remote I/O Head using

the thumbwheel switch on the faceplate.

Step 15. ReĆconnect the I/O cables to the I/O port connectors.
Step 16. Turn on power to the Remote I/O Head.
Step 17. ReĆconnect the BNC Tee Adapter from the Remote I/O

network to the BNC connector on the Remote I/O Head

faceplate.