Rockwell Automation 57C329 Remote I/O Communications, AutoMax User Manual

Page 39

Advertising
background image

3Ć13

TYPICAL BNC
CONNECTOR

FERRULE ON
ANVIL OF
CRIMPING DIE

SHOULDER ON
CONNECTOR BODY
BUTTS AGAINST DIE

Figure 3.14 Ć Connector Installation Step 9 for RGĆ59/U Cable

Step 10. Holdthe assembly in place andclose the crimp tool

handles until the rachet releases.

Step 11. Remove the crimpedassembly from the crimping dies.

The connector is now attachedto the coaxial cable. See

figure 3.15.

CRIMPED FERRULE

Figure 3.15 Ć Connector Attachedto RGĆ59/U Cable

3.4.4

Cable Segment Testing

Once a cable segment has been terminatedwith a connector on

each end, visually inspect the connector for loose connections,

nickedinsulation, or loose strands from the braidthat might cause a

poor connection or short. The center contact shouldbe straight and

centered inside the connector dielectric. Be sure that the center

conductor is inserted deep enough into the connector body. The tip

of the center contact shouldbe approximately even with the endof

the connector dielectric. Be sure the ferrule is crimped tightly against

the body of the connector andthat the shieldbraidwire does not

protrude from the ferrule.
Check the cable's mechanical connections by grasping the outer

conductor connector in one handandthe coaxial jacket in the other.

Pull firmly. The connectors should hold. Use a time domain

reflectometer to test for cable damage, shorts, and discontinuities.

Advertising