Error Code 31 is on the Processor

Module's LED Display

Problem: Error code 31" appears on a Processor module's LED

display. This error indicates the system has a problem accessing the

module though the backplane bus. A bus error may be caused by

removal of an I/O module, an I/O module failure, a rack backplane

failure, attempting to access an invalid address, or incorrect cabling

(45C8, 45C5).
Use the following procedure to isolate a bus error:
Step 1.

Decode the errorĆspecific information listed in the

Processor Info Log. See JĆ3650 or JĆ3669 for the

procedure for decoding bus errors.

Step 2.

Verify that the address being written to is a Read/Write

location. Read Only registers and bits cannot be written to

by application tasks.

Step 3.

Verify that the hardware is working correctly.
Systematically replace the Remote I/O module, the

Processor module(s), and the rack/backplane assembly,

one at a time, with a corresponding module or assembly

known to be operating correctly. After replacing each

module or assembly, if the problem is not corrected,

replace the original before going on to the next item.