Step 5.

Refer to figure 3.21 and use the following procedure to

connect input power to the Remote I/O Head:

240

240 VAC INPUT POWER

120 VAC INPUT POWER

M/N 57C328, M/N 57C329, and M/N 57C330

Figure 3.21 Ć 120 VAC or 240 VAC Input Power Connections

a.) Using a screwdriver, remove one of the screws from

the plastic guard covering the terminal strip and slide

the guard to the left to expose the terminals.

b.) Turn off and lock out or tag all sources of incoming

power. Make certain that no voltage is present on the

wires that will be used to provide 120 VAC or 240 VAC

input power.

c.) Using 14 AWG wire, connect the input power wires to

terminals L1 and L2.

d.) Connect the jumper wire to the corresponding

terminal, either 120 or 240 volts.

e.) Slide the guard back to cover the terminal strip and

replace the screw.

Step 6.

Set the drop number (1Ć7) of the Remote I/O Head using

the thumbwheel switch on the faceplate.
The drop number setting is recognized only at power up.

Therefore, make sure each drop on the network has a

unique drop number before power is applied. If more than

one drop is given the same drop number, transmission

collisions will occur on the line.