4Ć13

4.7.2.1

Configuration Task Example
The following is an example of a configuration task for the Remote

I/O network in figure 4.4. The two variables, DO_CFG% and

DO2_CFG_RDY@, are used to configure drop 2. It is not necessary

to configure drop 4 since it is an all digital rack as specified by the

setting of the Shark Interface module's rotary switch to the C"

position.
Note that a configuration task is required only if you are using

AutoMax Version 2.1 or earlier. If you are using Version 3.1 you must

upgrade to at least AutoMax Version 3.2 if you are using Shark drops.

If you are using AutoMax Version 3.2 or later, you use the AutoMax

Programming Executive Software to assign symbolic names to the

same physical I/O points.

10

! Shark RIO example

20

!

30

!

100

TASKEX[TYPE=BASIC, PRIORITY=7, SLOT=0, CRITICAL=FALSE]

110

TASKEXPC[TYPE=PC, PRIORITY=8, SLOT=0, CRITICAL=FALSE]

120

!

1100

!ąăremote I/O network protection

1200

!

1300

IODEF

RIO_D02@[SLOT=8,REGISTER=4,BIT=2]

1400

IODEF

RIO_D04@[SLOT=8,REGISTER=4,BIT=4]

1500

!

1600

!ąăShark drop 2 (mixed rack)

1700

!

1800

RIODEF

D02_CFG%[MASTER_SLOT=8,DROP=2,SLOT=0,REGISTER=0]

1900

RIODEF

D02_CFG_RDY@[MASTER_SLOT=8,DROP=2,SLOT=0,

&

REGISTER=0,BIT=15]

2000

RIODEF

SPD_REF%[MASTER_SLOT=8,DROP=2,SLOT=1,REGISTER=0]

2100

RIODEF

SPD_IND%[MASTER_SLOT=8,DROP=2,SLOT=3,REGISTER=11]

2200

RIODEF

START@[MASTER_SLOT=8,DROP=2,SLOT=5,REGISTER=0,

&

BIT=5]

2300

!

2400

! Shark drop 4 (all digital rack)

2500

!

2600

RIODEF

ON@[MASTER_SLOT=8,DROP=4,SLOT=1,REGISTER=0,BIT=2]

2700

RIODEF

RUN@[MASTER_SLOT=8,DROP=4,SLOT=4,REGISTER=8,BIT=1]

2800

RIODEF

START_ON@[MASTER_SLOT=8,DROP=4,SLOT=4,REGISTER=8, &

BIT=5]

3200

MEMDEF RIONET_OK@

4.7.2.2

Ladder Logic Task Example
The following is an example of a Ladder Logic task for the Remote

I/O network in figure 4.4. This task verifies that both slave drops are

onĆline before application tasks use the speed reference value.

START

ON

1050

RUN

RIONET_

OK

RUN

START

START_

ON

2110

Input

1050

Input

Input

Input

RIONET_

OK

Input