Rockwell Automation 57C329 Remote I/O Communications, AutoMax User Manual

Page 55

Advertising
background image

3Ć29

Step 2.

Turn off power to the rack.

Step 3.

Disconnect the drop cable from the module faceplate.

Step 4.

Use a screwdriver to loosen the screws that hold the

module in the rack. Take the module out ofthe slot in the

rack.

Step 5.

Take the replacement module out ofits shipping container.

Take it out ofthe antiĆstatic bag, being careful not to touch

the connectors on the back ofthe module.

Step 6.

Insert the replacement module into the rack, making sure

it is wellĆseated in the rack.

Step 7.

Set the drop number ofthe module by using the two

thumbwheel switches on the module faceplate. The upper

switch is the most significant digit; the lower switch is the

least significant digit.

Step 8.

Attach the drop cable to the module faceplate.

Step 9.

Turn on power to the rack.

Step 10. Monitor status registers 15Ć18 in the drop 0 area in each

module using the Status command described in chapter

5. Ifthe values in these registers increase consistently over

a short period oftime, there is a communication problem.

Refer to chapter 6 for instructions on troubleshooting a

communication problem.

3.6.2

Replacing the Shark Interface Module

(M/N 57C554)

Use the following procedure to replace a module:

DANGER

THIS EQUIPMENT IS AT LINE VOLTAGE WHEN AĆC POWER IS CONNECTED.

DISCONNECT AND LOCK OUT ALL UNGROUNDED CONDUCTORS OF THE AĆC

POWER LINE. FAILURE TO OBSERVE THESE PRECAUTIONS COULD RESULT

IN SEVERE BODILY INJURY OR LOSS OF LIFE.

Step 1.

Turn off power to the rack and all external devices.

Step 2.

Turn off power to the Shark rack including any power to

the wiring leading to the rack.

Step 3.

Disconnect the drop cable from the Shark Interface

module's faceplate.

Step 4.

Remove the module from the rack.

Step 5.

Take the replacement module out ofits shipping container.

Be careful not to touch the connectors on the back of the

module.

Step 6.

Insert the replacement module into the rack. Be sure the

module is wellĆseated in the rack.

Step 7.

Set the drop number ofthe module using the 16Ćposition

rotary switch on the module faceplate.

Step 8.

Connect the drop cable to the 9Ćpin connector on the

module faceplate.

Advertising