6 configuration – Rockwell Automation 57C329 Remote I/O Communications, AutoMax User Manual

Page 66

Advertising
background image

4Ć4

For an M/N 57C330 Remote I/O Head slave drop,

DROP_TIME = [1.9 + (X x 0.08) + (Y x 0.036)] milliseconds

where: X =

Total number of output registers being transferred

to the slave drop

Y =

Total number of input registers being transferred

from the slave drop

For an M/N 57C328 Remote I/O Head drop,

DROP_TIME=[1.7 + R  0.036] milliseconds

where: R = number of connected rails
For a Remote Drive Interface Head slave drop,

DROP_TIME = 2.1 milliseconds

For a Shark slave drop (all digital I/O) with a drop number of9

to F,

DROP_TIME = 1.8 milliseconds

For a Shark slave drop (analog and digital I/O) with a drop

number of1 to 7,

DROP_TIME = 4.0 milliseconds

The update period of each I\O register on the Remote I/O network is

equal to the sum of the drop time for each drop on the network plus

2.7 milliseconds to poll any inactive drops.
For example, a Remote I/O network with four drops has the following

update rate:

Drop 1, Multibus Rack: 5 inputs, 8 outputs

Drop 2, Multibus Rack: 5 inputs, 6 outputs

Drop 3, Remote I/O Head: 6 inputs, 5 outputs

Drop 4, Digital Shark Rack
Drop 1 Time = [1.5 + (13 x .018)]

=ă1.734 msec

Drop 2 Time = [1.5 + (11 x .018)]

=ă1.698 msec

Drop 3 Time = [1.7 + (5 x .013) + (6 x .028)]

=ă1.933 msec

Drop 4 Time =

=ă1.900 msec

Time to poll inactive drops

=ă2.700 msec

Update period for each Remote I/O register

ąă9.965 msec

Each register on the Remote I/O network in this example will be

updated by the master Remote I/O module every 9.965 milliseconds.

4.6

Configuration

Before running any application tasks, the system must be configured

using the AutoMax Programming Executive software. The major

function of configuration is to assign meaningful symbolic names to

physical points in the system. This feature allows you to construct

application tasks using variable names instead of actual physical

locations.