5Ć6

where:

PORT

=

0Ć3

REGISTER =

0Ć3

I/O

= `

Ć No rail exists

`unknown' Ć Rail exists but it has not been

determined whether it is INPUT or

OUTPUT (M/N 57C330 only)

`INPUT'

Ć Rail exists and contains INPUT

modules

`OUTPUT'

Ć Rail exists and contains OUTPUT

modules

`INPUT/

OUTPUT'

Ć Rail exists (M/N 57C328 only)

5.2.3

Clear (C)

The Clear command is used to clear the twoĆdigit LAST RESET code

and the PORT RETRIEScounters. When C" is entered, CLEARED"

will be displayed for the LAST RESET and PORT RETRIES fields.

5.2.4

Read Port (R)

The Read Port command is used to read the registers on a rail

attached to the Head. When R" is entered, you will be prompted for

a port number. When the port number (0Ć3, followed by a carriage

return) is entered, the data from that particular port will be displayed.

Data will be displayed in hexadecimal, decimal, and binary format:
REGISTERąI/OąHEXąDECąBIN

5.2.5

Write Port (W)

Entering W" enables you to write data to an output rail or an output

register on a drive. This command is valid only when the serial line is

inactive. Data can be written in decimal (default format), in

hexadecimal, or in binary.

WARNING

BEFORE PERFORMING THE WRITE SLOT COMMAND, THE USER MUST VERIFY

THAT THE OUTPUTS ARE EITHER ELECTRICALLYDISCONNECTED OR WILL

NOT CAUSE UNEXPECTED MACHINE MOTION IF ENERGIZED. FAILURE TO

OBSERVE THESE PRECAUTIONS COULD RESULT IN BODILYINJURY.

You must respond to the following prompts:
WRITE PORT: Enter the port number (0Ć3) followed by a carriage

return.

REGISTER: Enter the register number (0 to 3) followed by a

carriage return.

At this point, if the entered rail location cannot be written to because

the register does not exist or the rail is an input rail, the appropriate

error message will be displayed and the operation will be terminated.