Rockwell Automation 57C329 Remote I/O Communications, AutoMax User Manual

Page 52

Advertising
background image

3Ć26

wires that will be used to provide 120 VAC or 240 VAC

input power.

c.) Using 14 AWG wire, connect the input power wires to

terminals L1 and L2.

d.) Connect the jumper wire to the corresponding

terminal, either 120 or 240 volts.

e.) Slide the guard back to cover the terminal strip and

replace the screw.

Step 6.

Set the drop number (1Ć7) of the Remote Drive Interface

Head using the thumbwheel switch on the faceplate.
The drop number setting is recognized only at power up

or after a self test function. Therefore, make sure each

drop on the network has a unique drop number before

power is applied. If more than one drop is given the same

drop number, transmission collisions will occur on the line.
The Remote Drive Interface Head can be used only as a

slave drop (drop numbers 1Ć7, inclusive). Switch settings

0, 8 and 9 are invalid. If the thumbwheel switch is set to an

invalid drop number, error code A" will be displayed on

the sevenĆsegment LED on the Remote Drive Interface

Head's faceplate after power up. To clear the invalid drop

number fault code, refer to chapter 6.

Step 7.

To connect the module to a fiberĆoptic network, go to step

9. If you are connecting the module to a coaxial cable

network, continue to step 8.

Step 8.

Connect the BNC Tee Adapter from the Remote I/O

network to the BNC connector on the Remote Drive

Interface Head faceplate. Continue to step 10.

Step 9.

To connect the module to a fiberĆoptic network, a

twistedĆpairĆtoĆcoax balun (AMP 555053Ć1 is

recommended) is used to convert the cable between the

module and the transceiver as shown in figure 3.23. The

balun is connected to the module via the BNC Tee

Adapter. Note that a 75 ohm terminating load (M/N 45C71)

is required. Refer to figure K2.2 in Appendix K and

connect the twisted pair wire to the transceiver. Continue

to step 10.

1

P

S

HUB CONTAINING

RACKĆMOUNTED TRANSCEIVERS

COAXIAL

CABLE

TWISTED

PAIR WIRE

FIBERĆOPTIC

CABLE

STANDĆALONE

TRANSCEIVER

BALUN

TEE ADAPTER

TERMINATING LOAD

REMOTE DRIVE INTERFACE HEAD

Figure 3.23 Ć Connecting the Remote Drive Interface Head to the

FiberĆOptic Network