Rockwell Automation 57C329 Remote I/O Communications, AutoMax User Manual

Page 69

Advertising
background image

4Ć7

access to registers defined as INPUT. All other registers (those

without rails connected) will have no access allowed.
Whenever the rail configuration is to be physically changed (i.e., rails

added or removed), the drop should first be disconnected from the

network (disconnect the BNC Tee Adapter from the Remote I/O

Head). The drop should then be powered down before the rail

configuration is modified.

WARNING

INPUTS SHOULD NOT BE FORCED. DURING A POWER CYCLE, THE FORCED

INPUTS ARE INTERPRETED AS OUTPUTS AND, THEREFORE, WILL NOT

FUNCTION PROPERLY. FAILURE TO OBSERVE THIS PRECAUTION COULD

RESULT IN BODILY INJURY.

4.6.4

Remote Drive Interface Head Configuration

The Remote Drive Interface Head can control up to four drives that

use a railĆtype interface (e.g., the Reliance V★S GPĆ2000/VTAC V

controller). The AutoMax Remote Drive Interface Head must not

be connected to Local Heads, digital rails, or Analog Rails, LED

modules, or Thumbwheel Switch modules.
The Remote Drive Interface Head uses a fixed configuration of two

inputs and two outputs per I/O port. The Head assumes that the first

two registers (0 and 1) are AutoMax outputs (information to the drive)

and the second two registers (2 and 3) are AutoMax inputs

(information from the drive). This configuration cannot be changed.
The Remote Drive Interface Head will communicate with a device

connected to a port only if that device responds as a Local Head.

The Head will not reset when communication reĆtries to a port are

exhausted. The Ready Relay will not drop out. The Head will clear

input registers and continuously attempt to reĆestablish

communication with the device connected to the port.
AutoMax application tasks must be used to determine whether a

drive is communicating with the Head using a register or bit

generated by the drive. Refer to the documentation for the Rail

Interface module (D2Ć3170) and the GPĆ2000/VTAC V Main Controller

Installation, Operation and Maintenance instruction manual for more

information.

WARNING

REMOVING OR INSERTING A MODULE OR I/O INTERCONNECT CABLE WITH

POWER APPLIED MAY RESULT IN UNEXPECTED MACHINE MOTION OR LOSS

OF PROCESS CONTROL. STOP THE MACHINE OR PROCESS IN AN ORDERLY

FASHION AND DISCONNECT THE POWER TO THE SYSTEM BEFORE YOU

REMOVE OR INSERT A MODULE OR I/O INTERCONNECT CABLE. FAILURE TO

OBSERVE THESE PRECAUTIONS COULD RESULT IN BODILY INJURY.

Whenever the configuration is to be physically changed (i.e., drives

added or removed), the drop should first be disconnected from the

network (disconnect the BNC Tee Adapter from the Remote Drive

Interface Head). The drop should then be powered down before the

configuration is modified.