Publication DNET-UM072C-EN-P - July 2004

Determine Power Requirements 4-23

One power supply (middle-connected)

Example using thick cable

This example is used to check loading on both sides of a middle-connected
supply on a thick cable trunk line. Keep the loads, especially the higher ones,
close to the power supply. If the device location is fixed, put the power supply
in the center of the highest current concentration.

According to the look-up method, section 1 is operational while section 2 is
overloaded.

1. Find the voltages for each device in section 1 using the equation for

thick cable.

SUM {[(L

n

x (0.0045)) + (N

t

x (0.005))] x I

n

} < 4.65V.

A.[(100 x (0.0045)) + (1 x (0.005))] x 0.25 = 0.12V

B.[(400 x (0.0045)) + (2 x (0.005))] x 0.25 = 0.45V

C.[(800 x (0.0045)) + (3 x (0.005))] x 0.25 = 0.90V

2. Add each device’s voltage together to find the total voltage for section 1.

0.12V + 0.45V + 0.90V = 1.47V

power

supply

D3

PT

T

TR

TR

T

T

T

T

T

section 1

244 m

(800 ft)

122 m

(400 ft)

section 2

D2

D1

D4

D5

D6

30 m

(100 ft)

60 m

(200 ft)

122 m

(400 ft)

244 m

(800 ft)

0.25A

0.25A

0.25A

0.25A

1.5A

0.5A

TR = terminating resistor T = T-Port tap
PT = Power Tap D = device

31515-M

Value of

Section 1

Section 2

Total maximum current

1.25A (approximately)

1.25A (approximately)

Total current required

0.75A

2.25A

D1

0.25A

D2

0.25A

D3

0.25A