Rockwell Automation DeviceNet Media Design Installation Guide User Manual
Page 24

Publication DNET-UM072C-EN-P - July 2004
1-14 Get Started
•
open-style terminating resistors. 121
Ω
, 1%, 1/4W or larger resistors
connecting the white and blue conductors in micro- or mini-style attach
to:
– open-style T-Port taps
– trunk lines using terminator blocks
•
KwikLink flat cable terminating resistors
The 121
Ω
resistor is contained in the snap-on interface module:
•
sealed terminator with an Insulation Displacement Connector (IDC)
base (NEMA 6P, 13; IP67) catalog number 1485A-T1E4
•
unsealed terminator with IDC base (no gaskets) (NEMA 1; IP60)
catalog number 1485A-T1H4
Network end caps are included with each KwikLink terminator; see page 3-14
for complete installation instructions.
Wire
Color
Wire
Identity
Usage
Round
Usage
Flat
white
CAN_H
signal
signal
blue
CAN_L
signal
signal
bare
drain
shield
n/a
black
V-
power
power
red
V+
power
power
Blue
Red
Black
White
Shield or Bare
121
Ω
41827
Catalog number 1485A-C2
end cap
terminating resistor with end cap
30490-M
30479-M