Install class 1 kwiklink power cable – Rockwell Automation DeviceNet Media Design Installation Guide User Manual

Page 75

Advertising
background image

Publication DNET-UM072C-EN-P - July 2004

Make Cable Connections 3-15

3. Repeat the end cap installation process as outlined previously. Close the

IDC base and continue with connection as illustrated in the standard
installation instructions starting on page 3-10.

Install Class 1 KwikLink power cable

Install Class 1 KwikLink power cable as you would network cable. Refer to
page 3-10 for installation instructions. You can use auxiliary power cable
with the ArmorBlock MaXum cable base (1792D-CBFM) and I/O modules
(1792D series). When running cable into an enclosure, use flat cable gland
1485A-CAD.

.

30481

30482

30483

Class 1Auxiliary Power Cable

Spool size

Catalog number

75 m (246 ft)

1485C-P1L75

200 m (656 ft)

1485C-P1L200

420 m (1378 ft)

1485C-P1L420

Auxiliary Power Cable

Wire
Color

Wire
identity

Use

white

user
defined

user
defined

blue

user
defined

user
defined

black

V-

output
power

red

V+

output
power

30493-M

black PVC jacket

red and black
dc power pair 16 awg

white and blue
user defined pair 16 awg

5.3 mm (0.21 in.)

19.3 mm
(0.76 in.)

2.50 mm
(0.10 in.)