Determine the maximum trunk line distance

The distance between any two points must not exceed the maximum cable
distance allowed for the data rate used.

TIP

Round cable (both thick and thin) contains five wires: One
twisted pair (red and black) for 24V dc power, one twisted
pair (blue and white) for signal, and a drain wire (bare).

Flat cable contains four wires: One pair (red and black) for
24V dc power; one pair (blue and white) for signal.

Drop cable for KwikLink is a 4-wire unshielded gray cable.
It is used only with KwikLink flat cable systems.

Data rate

Maximum
distance
(flat cable)

Maximum
distance
(thick cable)

Maximum
distance
(thin cable)

125k bit/s

420m (1378 ft)

500m (1640 ft)

100m (328 ft)

250k bit/s

200m (656 ft)

250m (820 ft)

100m (328 ft)

500k bit/s

75m (246 ft)

100m (328 ft)

100m (328 ft)

Wire
Color

Wire
Identity

Usage
Round

Usage
Flat

white

CAN_H

signal

signal

blue

CAN_L

signal

signal

bare

drain

shield

n/a

black

V-

power

power

red

V+

power

power

The maximum cable distance is not
necessarily the trunk length only. It is the
maximum distance between any two devices.