Important – Rockwell Automation DeviceNet Media Design Installation Guide User Manual
Page 66

Publication DNET-UM072C-EN-P - July 2004
3-6 Make Cable Connections
To attach a PowerTap:
1. Cut and strip the thick cable back approximately 100 mm
(4 in.).
2. Loosen the gland nut.
3. Insert the cable into the PowerTap through the large cable gland until
approximately 3 mm (0.12 in.) of the cable jacket protrudes.
4. Firmly tighten the gland nut to provide strain relief and sealing.
IMPORTANT
The two fuses used in the PowerTap tap are 7.5A
fast-acting automotive type (ACT type), which you can
order from your local fuse supplier.
TIP
Cable used for input from a power supply should have the
white and blue leads cut off short.
ATTENTION
You must hold the hex flange with the cable gland wrench
during tightening.
31512-M
100mm (4 in)
Wire
Color
Wire
identity
Use
white
CAN_H
signal
blue
CAN_L
signal
bare
drain
shield
black
V-
power
red
V+
power
re
d
wh
it
e
dr
a
in
bl
u
e
bl
a
c
k
bl
ac
k
bl
u
e
dr
a
in
wh
it
e
re
d
red
black
drain
41757