3-6 Make Cable Connections

To attach a PowerTap:

1. Cut and strip the thick cable back approximately 100 mm

(4 in.).

2. Loosen the gland nut.

3. Insert the cable into the PowerTap through the large cable gland until

approximately 3 mm (0.12 in.) of the cable jacket protrudes.

4. Firmly tighten the gland nut to provide strain relief and sealing.

IMPORTANT

The two fuses used in the PowerTap tap are 7.5A
fast-acting automotive type (ACT type), which you can
order from your local fuse supplier.

TIP

Cable used for input from a power supply should have the
white and blue leads cut off short.

ATTENTION

You must hold the hex flange with the cable gland wrench
during tightening.

31512-M

100mm (4 in)

Wire
Color

Wire
identity

Use

white

CAN_H

signal

blue

CAN_L

signal

bare

drain

shield

black

V-

power

red

V+

power

re

d

wh

it

e

dr

a

in

bl

u

e

bl

a

c

k

bl

ac

k

bl

u

e

dr

a

in

wh

it

e

re

d

red

black
drain

41757

Advertising