Rockwell Automation DeviceNet Media Design Installation Guide User Manual

Page 84

Advertising
background image

Publication DNET-UM072C-EN-P - July 2004

4-6 Determine Power Requirements

Figure 4.3 Two Power Supplies, (One-End Connected, One Middle-Connected);
Two Cable Segments, Round
Cable (Thick).

Network
Length
m (ft)

Maximum
Current (A)

260 (853)

8.00*

280 (919)

7.69*

300 (984)

7.21*

320 (1050)

6.78*

340 (1115)

6.41*

360 (1181)

6.07*

380 (1247)

5.76*

400 (1312)

5.49*

420 (1378)

5.24*

440 (1444)

5.01*

460 (1509)

4.80*

480 (1575)

4.73*

500 (1640)

4.66*

Segment A

Segment B

Network
Length
m (ft)

Maximum
Current (A)

0 (0)

8.00*

20 (66)

8.00*

40 (131)

8.00*

60 (197)

7.38*

80 (262)

5.71*

100 (328)

4.66*

120 (394)

3.94

140 (459)

3.40

160 (525)

3.00

180 (591)

2.68

200 (656)

2.43

220 (722)

2.22

240 (787)

2.08

Network
Length
m (ft)

Maximum
Current (A)

260 (853)

1.89

280 (919)

1.76

300 (984)

1.64

320 (1050)

1.54

340 (984)

1.46

360 (1050)

1.38

380 (1247)

1.31

400 (1312)

1.24

420 (1378)

1.18

440 (1444)

1.13

460 (1509)

1.08

480 (1575)

1.07

500 (1640)

1.05

Power Supply B

Total Length of trunk line, meters (feet)

C

ur

rent

(a

mper

es)

NEC/CE Code Maximum
Current Limit

Exceeds NEC CL2/CECode 4A limit.

Exceeds NEC CL2/CECode 4A limit.

Power Supply A

Network
Length
m (ft)

Maximum
Current (A)

0 (0)

8.00*

20 (66)

8.00*

40 (131)

8.00*

60 (197)

8.00*

80 (262)

8.00*

100 (328)

8.00*

120 (394)

8.00*

140 (459)

8.00*

160 (525)

8.00*

180 (591)

8.00*

200 (656)

8.00*

220 (722)

8.00*

240 (787)

8.00*