Publication DNET-UM072C-EN-P - July 2004

Identify Cable System Components 2-5

Class 2 (CL2) General Purpose Cable: Well-suited for less-demanding
applications than heavy-duty cable, this design features a micro-style connector
(catalog number 1485P-K1E4-R5) optimized for use with this pliable cable.

KwikLink Power Cable (CL1): Used to run an auxiliary bus to power
outputs, i.e. valves, actuators, indicators. KwikLink power cable is a Class 1
cable capable of supplying 24V of output power with currents up to 8A.

Connect to the Trunk Line

The cable system design allows you to replace a device without disturbing the
cable system’s operation.

IMPORTANT

1485-P1Kxxx cable cannot be used with KwikLink
heavy-duty connectors.

TIP

The ArmorBlock MaXum cable base, 1792D-CBFM, is
designed to use both the KwikLink network and Auxiliary
Power cables. Use this cable base with all ArmorBlock
MaXum output modules.

Class 2 (CL2) KwikLink General

Purpose Cable

Spool Size

Catalog Number

75 m (246 ft)

1485C-P1K75

200 m (656 ft)

1485C-P1K200

420 m (1378 ft)

1485C-P1K420

Class 1 (CL1) KwikLink Power Cable

Spool Size

Catalog Number

75 m (246 ft)

1485C-P1L75

200 m (656 ft)

1485C-P1L200

420 m (1378 ft)

1485C-P1L420

IMPORTANT

You must terminate the trunk line on each end with a 121

, 1%, 1/4W or larger resistor.